Earth
resistance measurementMI2124
- 2-pole, 3-pole, 4-pole earth resistance measurements
- Selective earth resistance measurement with clamp (no influence from
parallel earths; no opening of rust junctions is needed).
- Two clamp earth measurement for quick testing in urban areas (no opening
of rusty junctions).
Specific earth
resistance (p) measurement
True RMS current
measurement for determining problems on earth systems and conductors.
-Outstanding features even in presence of mains interference and high probe
resistance.
- Warnings indication for out of limits results and incorrect test
conditions.
- 1000 memory locations and PC Software for print-out of measurement
protocol.
- Socket for external battery charger.
- Auto power-off.

|
|
Technical Specification |
|
Earth Resistance (four lead method) |
|
Display range |
0.1 19.99 kΩ |
|
Resolution |
0.01, 0.1, 1, 10Ω |
|
Basic accuracy |
±(2 % + 3 D).... (0 ÷ 2kΩ) |
|
Test
voltage |
<40 V/ 125 Hz/sine wave |
|
Short-circuit test current |
<20 mA |
|
High noise rejection |
yes |
|
Aut potential and current probe res. test |
yes |
|
Earth Resistance (tour-lead method + clamp)
A 1018 |
|
Display range |
0 1 1.99 kΩ |
|
Other characteristics see under four-lead
method |
|
Earth Resistance (two test clamps) A 1018,
A 1019 |
|
Display range |
0 1 19.99 Ω |
20.0 100.0 Ω |
|
Basic accuracy |
±(10 % + 2 D) |
±(20 %) |
|
Specific Earth Resistance |
|
Standard Set Order No. MI
2124 |
|
Display range |
0÷1999 kΩ m (kΩ ft) |
|
- Instrument |
|
|
Calculation |
p =2p aRE |
|
- Test lead 4.5 m, (black) |
|
|
Distance between test rods |
1 ÷30 m (1
÷ 90 ft) |
|
- Test lead 4.5 m (green) |
|
|
Other characteristics see under four-lead
method |
|
- Test lead 15 m (red) |
|
|
Current (True RMS) A 1018, A 1019 |
|
- Earth test rod, 4 pcs |
|
|
Measurement principle |
current clamp 1 A / 1 mA |
|
- Instruction manual |
|
|
Display range |
0 ÷ 200 A |
|
-
Declaration of conformity |
|
Resolution |
0. 1; 1 mA; 0.01; 0.1; 1 A |
|
- Production verification data |
|
|
Basic accuracy |
± (5 % + 5 D) (0.5mA ÷200 A) |
|
- Declaration of warranty |
|
|
Nominal frequency |
50/60 Hz |
|
 |
|
General Characteristics |
|
|
Power supply |
6 V (4 V 1.5 V IEC LR14) |
|
|
Memories |
1000 measurements |
|
|
Degree of protection |
IP 54 |
|
|
Protection Classification |
double insulation |
|
 |
|
Computer connection |
RS 232 |
|
Overvoltage category |
CAT 111/300 V CAT 11/600 V |
|
Dimensions |
(w x h x l) 156 x 100 x 190 mm |
|
Mass |
ca 1.2 kg |
|
Windows Downloading Software
"Smart Link"
* The memories of SMARTEC
testers can store approximately 1000 measurement values
* Transfer of measurement values
via RS 232 serial port to a PC
* Print-out of tabular display
used as a measuring report
* Runs on Windows
9519812000/NT/XP |
 |
|
 |
Simple operation with only one selection switch and large start button |
|
|

|
Large custom designed display offers warning indication of incorrect or out
of limit results |
| |
 |
New modem compact design with protective plastic cover. Meets high degree of
protection IP 54 and pollution degree 2. Small size and easy to carry |
| |
|
OPTIONAL
ACCESSORIES
Order No.:
A 1111 Three phase adapter
A 1020 Soft carrying bag - small
A 1007 Carrying strap
A 1026 Test lead 20 m. red
A 1011 Universal test cable. 3 x 1.5m
A 1055 Universal test cable, 2 x 1. 5 m
A 1016 Test tip, red
A 1015 Test tip, blue
A 1014 Test tip , black
A 1013 Alligator clip (black)
A 1064 Alligator clip (red)
A 1045 Fast battery charger
(230 VAC and/or 12 V DC) with
a set of 4 NiCd batteries
A 1050 Windows Software "Smart Link
with RS 232 interface cable
|