MI2121 |
|
| |
 |
Fast testing of(10, 30, 100, 300, 500 mA) both standard and selective types,
AC type. Test current multipliers of x 0.5, x 1, x 5
for checking of the trip out time on limit current values. Selectable
phase angle 0o (positive), 180o (negative). |
| |
RCD trip-out
current (l∆) measurement with high resolution test ramp. |
| |
RCD
trip-out time (t∆) measurement at nominal
differential current in accordance with the standards. |
| |
Contact voltage (Uc) measurement for checking of Earthing System. |
| |
LOOP
(EARTH) resistance measurement without tripping the RCD. |
Measurement of VOLTAGE
between LINE and Neutral and frequency measurement. |
|
Technical
Specification |
|
|
Measurement of VOLTAGE
between LINE and PE conductor and frequency
measurement. |
|
RCD Test |
|
|
|
|
| Test Current |
|
AC |
- 1000 memory locations and PC Software for
print-out of measurement protocol. |
| RCD Type |
|
Standard selective |
| Nominal
test currents(mA) |
10, 30, 100, 300,
500 |
- Warning indication of incorrect or out of
limit results. Socket for external battery charger. Auto power-off. |
|
Multiplicators of I∆N |
½,1,5 |
|
|
Trip out time (standard or selective RCDs) |
|
|
Measuring time (ms) |
0 ÷ 300
(500,selective), 0 ÷ 40 (150 selective) |
- Socket for
external battery charger |
|
Resolution (ms) |
1 |
|
|
|
|
- Auto power-off |
| Accuracy |
± 3ms |
|
 |
|
|
Trip out current I∆
(standard RCDs) |
|
|
| Range
I∆ |
|
(0.2 ÷ 1.1)
I∆N |
|
| Resolution |
0.05
I∆N |
|
| Accuracy |
± 0.1
I∆N
|
|
|
|
Contact voltage Uc |
|
|
|
|
|
|
Measuring range Uc (V) |
0 ÷ 99.9 |
|
| Resolution (V) |
0.01, 0.1 |
|
| Accuracy |
-0/+% of reading ±
0.2V |
|
|
Voltage UL-N,UL-L,UL-PE |
|
Frequency |
|
|
|
|
| Measuring range (V) |
0 ÷ 440 |
45.0 ÷ 65.0Hz |
|
| Accuracy |
±(3% of reading + 3V) |
± 0.2Hz |
|
Standard Set |
|
Order No. MI2121 |
|
| -
Instrument |
|
|
|
|
|
| Nominal frequency
range |
DC, 45 ÷65Hz |
|
- Mains
measuring cable, 1.5 m |
 |
|
|
R LOOP(no
RCD trip out) RLOOP=Uc/I∆N |
|
|
-
Instruction manual |
|
|
Measuring range (Ω) |
0 ÷ 2000 |
|
-
Declaration of conformity |
|
| Accuracy |
(consider accuracy of Uc) |
-
Production verification data |
|
| Test current |
I∆N/2 |
|
-
Declaration of warranty |
|
|
|
|
|
|
OOptional
Accessories |
|
|
|
 |
|
|
- Universal test
cable 3 x 1.5 m |
Order No. A 1011 |
|
|
- Alligator clip
(black) |
Order No. A 10 13 |
|
|
|
- Test tip (blue) |
Order
No. A 1015 |
|
|
|
- Test
tip (black) |
Order
No. A 10 14 |
|
|
|
- Soft
carrying bag - small |
Order
No. A 1020 |
|
|
|
-
Carrying strap |
Order
No. A 1007 |
|
|
| |
- Fast
battery charger (230 V AC and/or12 V DC) with a set of 4 NiCd batteries |
Order No. A 1045
|
|
|
|
| - Windows Software
"Smart Link"with RS232 interface cable |